ULTRASTAT-SC
ELECTRICAL
PROPERTIES:
PTP: 2.5 x 104 to 106 per
NFPA-99 @ 500 V
RTG: 2.5 x 104 to 106 per
EOS / ESD S7.1
STATIC DECAY:
Conditioning: 50% RH +/-2%@23°C+/-1° for
24 Hours
Test conducted @: 50% RH+/-2%@23°C+/-1°C
Test results=Time, seconds to decay to 10% of
initial charge
Results, <0.01 seconds
ULTRASTAT-SD
ELECTRICAL PROPERTIES:
PTP: 2.5 x 106 to 108 per
NFPA-99 @ 500 V
RTG: 2.5 x 106 to 108 per
EOS / ESD S7.1
STATIC DECAY:
Conditioning: 50% RH +/-2%@23°C+/-1° for
24 Hours
Test conducted @: 50% RH+/-2%@23°C+/-1°C
Test results=Time, seconds to decay to 10% of
initial charge
Results, <0.02 seconds
OTHER PROPERTIES:
ASTM F 1700
Passes
Underwriters Laboratories
Meets UL Standard
NFPA Life Safety Code 101
Class I Interior Floor Finish
Critical Radiant Flux (ASTM E 648)
Ultrastat-SC >1.08 W / cm2
Ultrastat-SD >1.03 W / cm2
Smoke Density Test (ASTM E 662)
<450
Flame Spread (ASTM E 84)
<75
Static Load Limit (Modified ASTM F 970-93)
1,500 psi
CONSTRUCTION:
Composition:
Homogeneous solid vinyl tile that has encapsulated conductive elements
of the carbon family distributed throughout the tile.
Gauge:
1/8"
Nominal Sizes:
12" x 12", 36" x 36"
Custom Sizes Available:
24" x 24" available in selected colors only.
INSTALLATION:
Adhesive & Spread Rate:
#150 Conductive Epoxy Adhesive; Covers 150 square feet / gallon.
Trowel Size:*
Type one: 1/16"x1/16" Square Notch with 1/16" Flats
Type two: 1/16"x1/16" Half Circular Notch with 1/32" Flats
Grounding:
One 2"x 24" copper strip installed every 2,000-2,500 feet.
Trowel size is dependent
upon tile size, surface type and condition,
Please refer to installation
instructions for proper trowel size selection. |